Auto Light Dark
Auto Light Dark

Measurements & Inspections User Guide

Measurements and Inspections are in Early Access Package (EAP): the feature is partially released and usable, but only enabled on request while we collect feedback; it is not part of the current subscription and may become an additional subscription later.

CORTEX Service now lets technicians record Measurements (such as Earth Fault Detection) and complete Inspections(such as a CCR preventive-maintenance checklist) directly on an asset, and lets managers review the results across the airfield in two new Cockpit views.

Both features live in a new Measurements & inspections section of the asset information panel. Every save is kept as its own dated record, so the full history stays available for audits.


Measurements

Inspections

Purpose

Track a numeric value over time

Prove a checklist was completed

Example

Earth fault detection (EFD) in MΩ

CL2051 Semi-annual Preventive Maintenance of CCR

Result per record

Value + status: Normal, Warning or Alarm

Each topic: Conform, Non-conform or Unknown

Asset view

Latest value, trend chart, previous records

Number of non-conforming topics

Cockpit view

Cockpit > Measurements

Cockpit > Inspections

Export

Excel per asset and from the Cockpit

Excel per asset and from the Cockpit

Common actions on the asset panel

  1. Select an asset on the map to open its information panel.

  2. Scroll to Measurements & inspections and click + Add.

  3. Choose a Record type (for example EFD or CL2051-SemiAnnually Preventive Maintenance of CCR Rev.00), fill it in and click Save.

  4. Each record type then shows as a card with these actions:

    • Record new values — add a new record of the same type.

    • Eye icon — view the latest record, including who reported it and when.

    • Download icon — export all records of that type for this asset to Excel.

    • Bin icon — delete the latest record.

    • Previous records — expand to see older records.


image-20261110-075540.png


Measurements

Measurements let you log a numeric value on an asset and see at a glance whether it is healthy. The first available measurement is Earth fault detection (EFD), recorded in MΩ on regulators (CCRs). For EFD, a higher value is better.

Record a measurement

  1. Select the regulator on the map.

  2. In Measurements & inspections, click + Add and choose EFD as record type (or click Record new values on an existing EFD card).

  3. Enter the value in Earth fault detection (EFD) (MΩ) and click Save.

  4. The EFD card updates with the new value, its status and the time of the latest record.

How the status is calculated

Each value is compared against the thresholds configured for the field. In the current set-up:

Status

Rule for EFD

Normal

10 MΩ or higher

Warning

Below 10 MΩ

Alarm

Below 1 MΩ

Out-of-range values can always be saved; they are flagged, not blocked. Hover the status to see a reminder that it is based on the field thresholds.

Read the trend on the asset

Below the card, the Earth fault detection (EFD) chart shows every recorded value over time, with the Warning and Alarm limits drawn as dashed lines.

  • Hover a point to see its value and date.

  • Use the < > arrows to step through individual records. When you are not on the latest record, an orange banner says You are not accessing the most recent measurement data.

  • Click the open icon next to a record to see the full record.

Review all regulators in the Cockpit

The Cockpit shows a Measurements tile with the number of devices that need attention (for example 1 / 2 devices). Click it to open Cockpit > Measurements:

  1. Pick the Measurement field (for example Earth fault detection (EFD)). A note explains that each asset is assessed on its latest recording in the selected period.

  2. Status tiles count assets per status: Alarm, Warning, Normal, Unknown and No recordings in selected period. Each tile has shortcuts to filter, show on the map, show the chart or jump to the table.

  3. Problems in selected period by sub-area shows where Warnings and Alarms sit.

  4. Recorded measurement statuses over time shows how statuses evolve.

  5. Measurement over time plots each asset as its own line against the thresholds. A note lists the thresholds that were valid when the values were recorded.

  6. Asset measurement results lists every asset with its latest reading. Filter by form, status, sub-area, value range or reading date. Per row you can view the record or show the asset on the map.

Use the period selector (calendar icon) to change the time range, and the download icon to export the results to Excel.


Screenshot 2026-11-10 at 08.54.37.png


Inspections

Inspections replace paper checklists: each topic is marked Conform or Non-conform, and the result is stored as audit evidence on the asset. The first available inspection is CL2051-SemiAnnually Preventive Maintenance of CCR Rev.00, with 13 topics.

Complete an inspection

  1. Select the regulator on the map.

  2. In Measurements & inspections, click + Add and choose the inspection as record type.

  3. The checklist opens as a table: one row per Inspection topic, with a Status and a Comment column. Topics marked * are required.

  4. Tap a status to cycle through the results: Unknown → Conform → Non-conform.

  5. Add a comment where useful, for example the measured value (205V) when a topic is Non-conform.

  6. Click Save once all required topics have a result.

The CCR checklist covers cleaning, damaged components, internal wiring, network connections, input voltage, output current, power factor (from ALCMS), current regulation on all brightness steps, and the readings on steps 1 to 5.

image-20261110-075835.png

Read the result on the asset

The inspection card shows how many topics failed, for example 1/13 non-conform, and the time of the latest record. Click the eye icon to open the full record, with each topic, its status and comment, who reported it and when. Use the download icon to export all inspection records of the asset to Excel.

Review all inspections in the Cockpit

The Cockpit shows an Inspections tile with the number of assets that have non-conformities. Click it to open Cockpit > Inspections:

  1. Summary tiles show Submissions, Conforming assets, Non-conforming assets and Assets with submissions.

  2. Submissions over time by form shows how many records were submitted per form.

  3. Most frequent non-conforming fields shows which checks fail most often.

  4. Submitted forms lists every submission with its date, asset, form and the non-conforming topics. Search by asset, or filter by conformity or form. Per row you can view the record or show the asset on the map.

Use the period selector to change the time range and the download icon to export the list to Excel.

Good to know

  • Web only for now. Measurements and inspections are recorded in the web application; iOS support follows later.

  • Predefined forms. The EFD measurement and the CCR inspection are provided by ADB SAFEGATE. Contact us if you need another measurement or checklist.

  • No automatic observations yet. A Non-conform result is shown on the asset and in the Cockpit, but does not create an observation. Create one manually from Open Observations if follow-up is needed.

  • Thresholds are kept with each record. If thresholds change later, older records keep the thresholds that were valid when they were recorded.

  • Nothing is overwritten. Every save creates a new record, so the history is complete for audits.

FAQ

Does a poor EFD value make the regulator unserviceable? No. EFD is a condition warning; it does not change the serviceability of the asset.

Can I save a value outside the expected range? Yes. The value is saved and flagged as Warning or Alarm.